Product Description
Stranded, circular compressed conductors (aluminum, aluminum-alloy, copper). Black extruded semi-conducting conductor screen. Outer insulation: black weather/UV-resistant thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE). This standard covers both constructions, rated for normal service temperatures of 75°C or 90°C.
Application
For 10kV aerial insulated cables. Primarily used for overhead electrical energy distribution under normal conditions. Conductors must be installed on insulators and/or spacers suitable for the service voltage. Consider dielectric compatibility of the covering, insulators, spacers, etc.
Applicable Standard
GB/T 14049 (Equivalent to IEC 60502-2)—10kV Rated Voltage Aerial Insulated Cables
Technical Parameters
| Nominal Size |
Min. No. of Wires |
Approx.Dia of Conductor |
Min. Thickness of Conductor Screen |
Nominal Thickness of Insulation | Nominal Thickness of Insulation Screen |
Max.DC Resistance at 20°C | Min.Breaking Load Hard Copper |
||
| Reduced | Nominal | Hard Copper |
Soft Copper |
||||||
| mm² | No. | mm | mm | mm | mm | mm | Ω/km | Ω/km | N |
| 10 | 6 | 3.8 | 0.5 | 3.4 | 1.830 | ||||
| 16 | 6 | 4.8 | 0.5 | 3.4 | 1.150 | ||||
| 25 | 6 | 6.0 | 0.5 | 2.5 | 3.4 | 1.0 | 0.749 | 0.727 | 8465 |
| 35 | 6 | 7.0 | 0.5 | 2.5 | 3.4 | 1.0 | 0.540 | 0.524 | 11731 |
| 50 | 6 | 8.3 | 0.5 | 2.5 | 3.4 | 1.0 | 0.399 | 0.387 | 16052 |
| 70 | 12 | 10.0 | 0.5 | 2.5 | 3.4 | 1.0 | 0.276 | 0.268 | 23461 |
| 95 | 15 | 11.6 | 0.6 | 2.5 | 3.4 | 1.0 | 0.199 | 0.193 | 31759 |
| 120 | 18 | 13.0 | 0.6 | 2.5 | 3.4 | 1.0 | 0.158 | 0.153 | 39911 |
| 150 | 18 | 14.6 | 0.6 | 2.5 | 3.4 | 1.0 | 0.128 | 49505 | |
| 185 | 30 | 16.2 | 0.6 | 2.5 | 3.4 | 1.0 | 01021 | 61846 | |
| 240 | 34 | 18.4 | 0.6 | 2.5 | 3.4 | 1.0 | 0.0777 | 79823 | |
| 300 | 34 | 20.6 | 0.6 | 2.5 | 3.4 | 1.0 | 0.0619 | 99788 | |
| 400 | 53 | 23.8 | 0.6 | 2.5 | 3.4 | 1.0 | 00484 | 133040 | |
| Nominal Size |
Min.No. Of Wires |
Approx.Dia
of |
Min. Thickness of Conductor Screen |
Nominal Thickness of Insulation |
Nominal Thickness of Insulation Screen |
Max.DC Resistance at 20°C | Min.Breaking Load | |||
| Reduced | Nominal | AAC | AAAC | AAC | AAAC | |||||
| mm² | No. | mm | mm | mm | mm | mm | Ω/km | Ω/km | N | N |
| 10 | 6 | 3.8 | 0.5 | 3.4 | 3.080 | 3.574 | ||||
| 16 | 6 | 4.8 | 0.5 | 3.4 | 1.910 | 2.217 | ||||
| 25 | 6 | 6.0 | 0.5 | 2.5 | 3.4 | 1.0 | 1.200 | 1393 | 3762 | 6284 |
| 35 | 6 | 7.0 | 0.5 | 2.5 | 3.4 | 1.0 | 0.868 | 1.007 | 5177 | 8800 |
| 50 | 6 | 8.3 | 0.5 | 2.5 | 3.4 | 1.0 | 0.641 | 0.744 | 7011 | 12569 |
| 70 | 12 | 10.0 | 0.5 | 2.5 | 3.4 | 1.0 | 0.443 | 0.514 | 10354 | 17596 |
| 95 | 15 | 11.6 | 06 | 2.5 | 3.4 | 1.0 | 0.320 | 0.371 | 13727 | 23880 |
| 120 | 18 | 13.0 | 06 | 2.5 | 3.4 | 1.0 | 0.253 | 0.294 | 17339 | 30164 |
| 150 | 18 | 14.6 | 0.6 | 2.5 | 3.4 | 1.0 | 0.206 | 0.239 | 21033 | 37706 |
| 185 | 30 | 16.2 | 06 | 2.5 | 3.4 | 1.0 | 0.164 | 0.190 | 26732 | 46503 |
| 240 | 34 | 18.4 | 0.6 | 2.5 | 3.4 | 1.0 | 0.125 | 0.145 | 34679 | 60329 |
| 300 | 34 | 20.6 | 0.6 | 2.5 | 3.4 | 1.0 | 0100 | 0.116 | 43349 | 75411 |
| 400 | 53 | 23.8 | 06 | 2.5 | 3.4 | 1.0 | 0.0778 | 0.0904 | 55707 | 100548 |
| Size (mm²) |
No.and Dia. of Wires |
Conductor Diameter | Insulation Thickness | Cable Diameter | Rated Strength |
Weight | |
| AL | St | ||||||
| No. | No./mm | mm | mm | mm | kgf | kg/km | |
| 32 | 6/SB | 1/2.6 | 7.2 | 3.0 | 13.2 | 1090 | 210 |
| 58 | 6/SB | 1/3.5 | 9.7 | 3.0 | 15.7 | 1900 | 330 |
| 95 | 6/SB | 1/3.5 | 12.0 | 3.5 | 19.0 | 2360 | 530 |
| 160 | 18/SB | 1/3.2 | 15.4 | 4.0 | 23.4 | 3080 | 730 |
| 240 | 18/SB | 1/4.0 | 18.9 | 4.0 | 27.0 | 4500 | 1040 |