87/150KV High Voltage Power Cable

87/150kV HV cables fall into the category of EHV XLPE insulated power cables.

IEC 60840

Product Description

87/150kV HV cables fall into the category of EHV XLPE insulated power cables.

Application

As a core product for150kV EHV power transmission networks, they replace overhead lines of the same voltage class for underground/tunnel laying in urban power grids, industrial parks and cross-regional transmission projects. Featuring large transmission capacity, excellent insulation, strong anti-environmental interference and small floor space, they are widely used in overhead-to-underground transformation of main power grids, cross-sea/river transmission and power grid construction in urban core areas.

Applicable Standard

IEC 60840

Construction

1.Conductor: Circular Stranded Compacted Conductor(≤800mm2),Milliken Conductor(>800mm2)

2.Conductor Screen:Super Smooth Semi-Conductive Compound

3.Insulation: Super Clean Cross Linked Polyethylene(XLPE)

4.Insulation Screen:Super Smooth Semi-Conductive Compound

5.Binder Tape:Semi-Conductive Tape

6.Metal Sheath: Corrugated Aluminum Sheath/Lead Sheath/Aluminum Laminated Tape

7.Anti-Corrosive Layer:Cable Asphalt

8.Outer Sheath: Polyvinyl Chloride(PVC) or Polyethylene(PE)

9.Conductive Layer: Graphite

10.Optional: Copper Wire Screen,Metal Wire Screen  

Technical Parameters

Rated Voltage:87/150kV
Rated Voltage:87/150kV
YJLW03:CU/XLPE/CAS/HDPE   YJLW02:CU/XLPE/CAS/PVC     YJLLW03:AL/XLPE/CAS/HDPE    YJLLW02:AL/XLPE/CAS/PVC
Nominal area
of conductor
mm² 185 240 300 400 500 630 800 800* 1000 1200 1400 1600 1800 2000
Thickness of
insulation
  mm 22.0 21.0 21.0 21.0 21.0 21.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
Thickness  of
aluminum tape
  mm 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.3 2.3 2.3 2.3 2.3 2.3
Thickness of
outer sheath
  mm 4.0 4.0 4.0 4.0 4.0 4.5 4.5 4.5 4.5 5.0 5.0 5.0 5.0 5.0
Approx.outer
diameter
  mm 93.8 94.2 96.3 98.9 102.1 106.6 109.8 112.0 116.8 122.2 125.2 128.5 132.2 135.2
Approx.weight
(kg/km)
Cu 7361 7850 8594 9587 10862 12637 14355 14705 17261 19318 21412 23489 25464 27685
  Al 6282 6424 6802 7339 7938 8811 9437 9788 11074 12200 13067 13967 14838 15706
   Max.DC
resistance of
conductor  at
20℃(2/km)
Cu 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0221 0.0176 0.0151 0.0129 0.0113 0.0101 0.0090
  Al 0.1640 0.1250 0.1000 0.0778 0.0605 0.0469 0.0367 0.0367 0.0291 0.0247 0.0212 0.0186 0.0165 0.0149
Current ratings(A)
  Soil
∴
  Cu 463 538 606 690 784 888 997 1040 1164 1253 1344 1423 1490 1557
  Air
∴
  Cu 557 655 747 860 991 1140 1303 1363 1553 1692 1836 1966 2077 2192
  Soil
… ·
  Cu 532 620 699 794 900 1016 1138 1183 1309 1397 1485 1557 1615 1670
  Air
… ·
  Cu 567 668 761 875 1006 1155 1317 1374 1553 1683 1814 1929 2024 2121

 




      Related Products

      Wire and Cables Samples Available

      We work with clients to identify their exact application needs and technical specifications, enabling our
      technical team to provide tailored samples that meet all performance requirements.

      Have Questions?
      Get in Touch with Us.

      +86 188 3803 6118
      High-Tech Industrial Development Zone,Zhengzhou City,Henan Province,China

      Send Us a Message






        Your trusted partner in high- performance wire and cables